San Mateo County Transit District
Special DistrictCA
Jul 23, 2026
Closes
Aug 7, 2026
Emergency Generator Annual Maintenance
Provide labor and material to perform annual level II service for 2027 and 2028 on the following emergency generator units: See separate generator unit specifications sheet -One 350 Kw Kohler unit at the South Base Facility -One 450 Kw Kohler unit at the North Base Facility -One 12 Kw Cummins unit at the Brewster Facility -One 176 Kw BlueStar portable unit at North Base Facility Level II service is to include: 1. A complete inspection of equipment including condition of batteries, radiator fan and alternator drive belts, hoses, oil heater, radiator, coolant, fluid leaks. 2. Replace engine oil and oil filters – send an oil sample to lab for analysis. 3. Replace air filters 4. Replace fuel filters 5. Perform a two hour full load test on each unit.