500,000 Gallon Toroellipse (North Tank) Exterior Overcoat and Miscellaneous Repairs RFP

Description: The structure is a 500,000 gallon toroellipse elevated water storage tank with a high-water level of 137 feet, 4 inches. The work includes: Exterior: High pressure water clean (5,000 to 10,000 psi) and spot power tool clean to a SSPC-SP11 standard. Apply a three (3) coat epoxy urethane fluoropolymer system. Mixer: Install a mechanical mixer. Foundation: Water clean and apply a two (2) coat epoxy system. Repairs: 1)Replace the riser manway. 2)Replace the pit vault hatch. 3)Overflow discharge modification. 4)Install fall prevention devices on the leg and sidewall ladders. 5)Replace the wet interior ladder. 6)Balcony drain holes. 7)Install swing gates at the balcony opening and at the roof platform. 8)Install a handrail around the transition cone in the wet interior. 9)Adjust the loose sway rods. 10)Replace valves and pipe sections in the pit. 11)Relocate the electrical conduit on the sidewall and roof. 12)Install grounding rods for the structure.

Buyer
City of Decatur

City · IN, US

Released
Nov 5, 2026
Closes
Dec 8, 2026(16 days left)