Summary
Install new 600-amp outdoor electrical service in the same location as the existing 200amp electrical panel and meter socket. The service shall include a 600-amp single-phase CT cabinet, 4s 6-terminal meter socket, and breaker panels for the existing campsites. The panels shall have the capacity for two future 50/30/20-amp pedestals. The panels shall also have the capacity to uprate pedestals 1, 3, 5, 7, and 9. These pedestals are currently 30/20 amp and maybe uprated to 50/30/20 amp in the future. The proposal shall include installing new secondary wire from the existing transformer location to the new CT cabinet, mounting the meter socket, and wiring of the panels.