Summary
The contractor shall maintain existing bulk liquid oxygen tank and reserve tank with appropriate backup cylinders for reserve or equivalent to provide a minimum of 96 hours of reserve capacity. The contractor shall provide additional equipment accessory to the bulk tank to provide a complete bulk liquid oxygen distribution system including but not limited to; local pad alarm panel and telemetry monitoring system. Through the duration of the contract, the contractor shall be liable for the integrity, suitability, and safety of contractor owned tank(s)/cylinder(s) that will insure compliance with applicable regulations, standards and normal good practices. The tank capacity and reserve system are minimum capacities required by the using facilities. Manifold, auto-switching, liquid converter, alarm switch, regulator, valves, level indicator, and any other devices or connections required for proper tie-ins with the facility’s gas system shall be furnished by the contractor, without cost to the Government. The manifold or liquid converter shall deliver gas at a pressure and rate of flow adequate to supply the system. Each liquid oxygen storage container shall have an outlet that allows access for testing the purity of the oxygen.