Logo

starbridge

Book a Demo
RFPs/DCCU Temporary Dehumidification Package Rental

DCCU Temporary Dehumidification Package Rental

Naval Supply Systems Command

Summary

Desiccant Climate Controlled Unit (DCCU): 3.2.1. 10,000 CFM DCCU Physical Attributes: Physical Attributes: Maximum Dimensions 20’10” x 7’4” x 9’3” [L x W x H] Maximum Weight: 16,450 Lbs. All Components much be fully integrated within single housing. Electrical Power Requirements: 2 Circuits at [460 Volt AC / 3 Phase / 400A] each. Steam Requirements: 100 PSIG @ 338°F; 1 ½” FNPT. Condensate drain line must be fitted with a steam trap rated to a minimum 150 PSI. See attached file.